HUTIRA – PLYN
plyn@hutira.cz
+420 541 212 144
  • Hutira
    Menu

    Technical parameters

    RESO type (without measurement)

    Inlet pressure range: 10 – 40 bar
    Outlet pressure setting range: 0,34 – 5,5 bar
    RS output: up to 200 m3(n)/h
    one-row design = 1N
    two-row design = 2N

    RESO type with measurement

    Inlet pressure range: 10 – 40 bar
    Outlet pressure setting range: 0,34 – 5,5 bar
    RS output: up to 200 m3(n)/h
    With the possibility of measuring
    gas meter G10-G65 (DN50/171 mm)
    one-row design = 1M
    two-row design = 2M

    Custom RESO

    Inlet pressure range: 10 – 40 bar
    Outlet pressure setting range: 0,34 – 5,5 bar
    RS output: up to 650 m3(n)/h

    Advantages of the product

    • Regulator, monitor system
    • Proven solution with an emphasis on simplicity, safety and reliability.
    • Standard solutions are pre-prepared, including dimensionally suitable cabinets.
    HUTIRA RESO – Regulation set – HUTIRA | HUTIRA

    Overview of variants

    Regulation set HUTRA RESO 1N HUTIRA RESO 2N HUTIRA RESO  1M HUTIRA RESO 2M
    Dimensions inlet DNSO PN40 DN50 PN40 DN50 PN40 DN50 PN40
    Dimensions outlet DN5O PN16 DN50 PN16 DN5O PN16 DN50 PN16
    Pitch inlet/outlet 880 1180 1140 1180
    Suitable cabinet MAXIPOL 12124/2P SEF 80 SEF 70 SEF 80
    Cabinet size hxwxd [mm] 1250 x1250 x 420 1800 x 1935 x 720 1500 x 1755 x 585 1800 x 1935 x 720

    How does HUTIRA RESO work with a regulator-monitor system?

    The regulation line is equipped with two 627 regulators, which work with a monitor-regulator system. In the event of a failure of the regulator and an increase in pressure, its function is taken over by a monitor that is set to a higher pressure. Furthermore, 1 piece of ABR type OSE is preceded, which secures the outlet pipe against both an increase and a decrease in the outlet pressure. The set can be supplemented with a control safety valve (V/20-2).

    Why are HUTIRA RESO assemblies investment-friendly and operationally undemanding?

    Our design uses the FISHER 627 regulator, which does not require preheating under standard domestic conditions. It is therefore not necessary to install a pre-heater or build the electrical connection associated with it. The product is also pre-prepared in terms of production and technical documentation.

    Why are HUTIRA RESO assemblies safe and reliable?

    Our regulation sets (each series) always have two safety elements. We like to use the regulator-monitor system, which does not have to interrupt the gas supply to the customer immediately in the event of a problem (e.g. an increase in outlet pressure).

    For download

    Technical sheet HUTIRA RESO stáhnout
    Commissioning information stáhnout
    Drawing AutoCAD HUTIRA RESO 1N kontaktovat
    Drawing AutoCAD HUTIRA RESO 2N kontaktovat
    Drawing AutoCAD HUTIRA RESO 1M kontaktovat
    Drawing AutoCAD HUTIRA RESO 2M kontaktovat